MIC-30|MIC-10|MIC-5000兆欧表|波兰sonel MIC-30|MIC-10|MIC-5000兆欧表|深圳华清仪器专业代理,优惠价供应|MIC-30绝缘电阻测试仪|深圳华清仪器: 29806349 MIC-1000升级MIC-30绝缘电阻测试仪|深圳华清仪器总代理Insulation resistance measurement: - selected test voltage: any voltage in the 50...1000 V range with 10 V step,
- automatic measurement in sockets with the UNI-Schuko adapter with possibility of configuring pairs of measured cables,
- continuous indication of insulation resistance or leakage current,
- automatic discharge of capacitance of tested object after the insulation resistance measurement,
- acoustic signalling of five-second periods to facilitate obtaining time characteristics,
- measured test times T1, T2 i T3 to measure one or two absorption coefficients in the 1... 600 sec. range,
- indication of actual test voltage during the measurement,
- protection against measuring live objects,
- three-lead measurement.
Continuity measurement of protective and equipotential conductors according to EN 61557 - 4 with the >200 mA current Low-voltage circuit continuity and resistance measurement: - circuit resistance measurement (<1999 Ω ) with the <15 mA current,
- quick sound signal if circuit resistance is below 30Ω.
Leakage current measurement. Capacitance measurement during the RISO measurement Measurement of alternating and direct voltages in the 0...600 V range. 990 memory cells and wireless data transmission to a computer using the USB - OR-1 adapted. Power supply: 4 AA disposable or rechargeable batteries, monitoring of power supply voltage. Meters conform to EN 61557. Electric safety: - type of insulation: double, according to EN 61010 - 1 and IEC 61557
- measurement category: IV 600 V (III 1000 V) according to EN 61010 - 1
- protection class acc. to EN 60529: IP67
Other technical specifications: - power suply: 4 alkaline batteries or or battery package Ni-MH
- weight: ~1 kg
- dimentions: 220 x 100 x 60 mm
Insulation resistance measurement Measuring range according to EN 61557 - 2 for UN=50 V: 50 kΩ...250,0 MΩ Range | Resolution | Accuracy | 0,0...999,9 kΩ | 0,1 kΩ | ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]* | 1,000...9,999 MΩ | 0,001 MΩ | 10,0...99,99 MΩ | 0,01 MΩ | 100,0...250,0 MΩ | 0,1 MΩ |
*for the WS-04 lead Measuring range according to EN 61557 - 2 for UN=100 V: 100 kΩ...500,0 MΩ Range | Resolution | Accuracy | 0,0...999,9 kΩ | 0,1 kΩ | ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]* | 1, 000...9,999 MΩ | 0,001 MΩ | 10,0...99,99 MΩ | 0,01 MΩ | 100,0...500,0 MΩ | 0,1 MΩ |
*for the WS-04 lead Measuring range according to EN 61557 - 2 for UN=250 V: 250 kΩ...2,000 GΩ Range | Resolution | Accuracy | 0,0...999,9 kΩ | 0,1 kΩ | ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]* | 1,000...9,999 MΩ | 0,001 MΩ | 10,0...99,99 MΩ | 0,01 MΩ | 100,0...999,0 MΩ | 0,1 MΩ | 1,000...2,000 GΩ | 0,001 GΩ |
*for the WS-04 lead Measuring range according to PN-EN 61557 - 2 for UN=500 V: 500 kΩ...20,00 GΩ Range | Resolution | Accuracy | 0,0...999,9 kΩ | 0,1 kΩ | ±(3% m.v. + 8 digits) [±(5% m.v. + 8 digits)]* | 1,000...9,999 MΩ | 0,001 MΩ | 10,00...99,99 MΩ | 0,01 MΩ | 100,0...999,0 MΩ | 0,1 MΩ | 1,000...9,999 GΩ | 0,001 GΩ | ±(4% m.v. + 6 digits) [±(6% m.v. + 6 digits)]* | 10,00...20,00 GΩ** | 0,01 GΩ |
*for the WS-04 lead **for the WS-04 lead range to 10 GΩ Measuring range according to EN 61557 - 2 for UN=1000 V: 1000 kΩ...10,00 GΩ Range | Resolution | Accuracy | 0,0...999,9 kΩ | 0,1 kΩ | ±(3% m.v. + 8 digits) | 1,000...9,999 MΩ | 0,001 MΩ | 10,00...99,99 MΩ | 0,01 MΩ | 100,0...999,0 MΩ | 0,1 MΩ | 1,000...9,999 GΩ | 0,001 GΩ | ±(4% m.v. + 6 digits) | 10,00...99,99 GΩ | 0,01 GΩ | 100,0 GΩ | 0,1 GΩ |
Continuity measurement of protective and equipotential conductors with the 200 mA current Measuring range according to EN 61557 - 4: 0,10...1999 Ω Range | Resolution | Accuracy | 0,00...19,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) | 20,0...199,9 Ω | 0,1 Ω | 200...1999 Ω | 1 Ω | ±(4% m.v. + 3 digits) |
- Voltage on open terminals: <8 V
- Output current at R <2 Ω: ISC >200 mA: ISC >200 mA
- Compensation of test leads’ resistance
- Unidirectional current flow
Low-voltage and resistance measurement Range | Resolution | Accuracy | 0,0...199,9 Ω | 0,1 Ω | ±(3% m.v. + 3 digits) | 200...1999 Ω | 1 Ω |
- Voltage on open terminals: <8 V
- Current for closed terminals 5 mA < ISC < 15 mA
- Sound signal and green LED on when measured resistance < 30 Ω ± 50%
- Compensation of test leads’ resistance,
Capacitance measurements Range | Resolution | Accuracy | 1...999 nF | 1 nF | ±(5% m.v. + 5 digits) | 1,00...9,99µF | 0,01µF |
- Capacitance value displayed during the RISO measurement
- For test voltages below 100 V and measured resistance below 10 MΩ, unspecified capacitance measurement error
Measurement of alternating and direct voltage Range | Resolution | Accuracy | 0,0...299,9 V | 0,1 V | ±(2% m.v. + 6 digits) | 300...600 V | 1 V | ±(2% m.v. + 2 digits) |
Frequency range: 45...65 Hz MIC-30绝缘电阻测试仪|深圳华清仪器: 29806349 |